arXiv:2510. 00831v2 Announce Type: replace Abstract: The increasing complexity of modern power systems, driven by the integration of inverter-based and distributed energy resources, challenges the reliability of conventional protection schemes and motivates the use of machine learning for protection tasks.
By Julian Oelhaf, Georg Kordowich, Changhun Kim, Paula Andrea P\'erez-Toro, Christian Bergler, Andreas Maier, Johann J\"ager, Siming Bayer
EvEMTBench is an open, executable, and versioned benchmark designed to standardize the evaluation of machine‑learning methods for power system protection. It defines 12 protection and event‑analysis functions across four grids (20–345 kV) as 24 scored tasks, enabling structured assessment under varied observability, distribution shifts, and cross‑grid transfer scenarios. The benchmark includes committed data partitions, leakage controls, and reproducible reporting, and demonstrates that wider observability does not always help, that shifted conditions expose hidden failures, and that fault detection transfers better than fault localization.
By Julian Oelhaf, Georg Kordowich, Christian Bergler, Andreas Maier, Johann J\"ager, Siming Bayer
The paper evaluates three machine‑learning fault detectors—gradient‑boosted trees, a convolutional neural network, and logistic regression—against a reference sequence‑current method on 9,022 simulated 90 kV line fault episodes. Using a protection‑oriented assessment framework that includes multiple window conditions, causal labeling, episode‑grouped cross‑validation, and a fixed security budget, the authors report near‑perfect AUC‑ROC (>0.999) but reveal that missed‑trip rates can reach 1.99 % and false‑trip rates 0.12–0.16 % per window, with nuisance assertions in 11.3–19.1 % of episodes. The study also finds that higher fault resistance correlates most consistently with missed trips and that a fault‑current gradient is only partially captured by waveform‑derived current.
whyItMatters":"The assessment demonstrates that high aggregate performance metrics can mask significant protection‑relevant errors, highlighting the need for protection‑oriented evaluation of ML fault detectors."
By Julian Oelhaf, Georg Kordowich, Changhun Kim, Christian Bergler, Andreas Maier, Johann J\"ager, Siming Bayer
The study examines how machine‑learning fault detectors trained on data from specific relay locations perform when applied to other relays in a 110 kV transmission network. Using 50 ms windows and a multilayer perceptron, the authors evaluate all 64 source–target relay combinations and find that overall F1‑scores remain similar, but the false‑positive rate rises markedly while the false‑negative rate falls when models are transferred across relays. Analysis shows that models retain coarse bus‑group information, and that aggregate metrics can mask location‑specific changes in false‑alarm behavior, underscoring the need to assess error types separately for cross‑relay generalization.
By Nithin Pradeep Nadayil Kizhakkethil, Julian Oelhaf, Christian Bergler, Andreas Maier, Siming Bayer
arXiv:2607. 16031v1 Announce Type: cross Abstract: Data-driven pre-fault dynamic security assessment (DSA) rapidly evaluates the dynamic risk of credible contingencies on a power system using machine learning.
By Olayiwola Arowolo, Maosheng Yang, Jochen Cremer
The paper presents a machine‑learning framework for classifying power‑system contingencies into safe, moderate, or severe categories. Using Newton‑Raphson load flow data, the study applies SMOTE, PCA, and classifiers (KNN, Random Forest, SVM) to IEEE‑14 and IEEE‑30 bus systems, evaluating performance with precision, recall, and F1 score. Random Forest achieved the highest F1 scores, while PCA improved overall performance more than SMOTE, which boosted recall at the cost of some false positives.
By Joshua Salako, Folajimi Osikomaiya, Olakorede Olamiju