arXiv:2608. 20181v1 Announce Type: cross Abstract: Studies of machine-learning-based power-system protection increasingly report near-perfect scores, yet the meaning of those scores depends strongly on the evaluation setting.
By Julian Oelhaf, Georg Kordowich, Paula Andrea P\'erez-Toro, Christian Bergler, Johann J\"ager, Andreas Maier, Siming Bayer
The paper evaluates three machine‑learning fault detectors—gradient‑boosted trees, a convolutional neural network, and logistic regression—against a reference sequence‑current method on 9,022 simulated 90 kV line fault episodes. Using a protection‑oriented assessment framework that includes multiple window conditions, causal labeling, episode‑grouped cross‑validation, and a fixed security budget, the authors report near‑perfect AUC‑ROC (>0.999) but reveal that missed‑trip rates can reach 1.99 % and false‑trip rates 0.12–0.16 % per window, with nuisance assertions in 11.3–19.1 % of episodes. The study also finds that higher fault resistance correlates most consistently with missed trips and that a fault‑current gradient is only partially captured by waveform‑derived current.
whyItMatters":"The assessment demonstrates that high aggregate performance metrics can mask significant protection‑relevant errors, highlighting the need for protection‑oriented evaluation of ML fault detectors."
By Julian Oelhaf, Georg Kordowich, Changhun Kim, Christian Bergler, Andreas Maier, Johann J\"ager, Siming Bayer
arXiv:2609.16744v1 Announce Type: new
Abstract: The integration of renewable energy sources into the electrical grid introduces complex challenges in fault detection and coordination of grid recovery...
By Julian Oelhaf, Georg Kordowich, Paula Andrea P\'erez-Toro, Tom\'as Arias-Vergara, Andreas Maier, Johann J\"ager, Siming Bayer
EvEMTBench is an open, executable, and versioned benchmark designed to standardize the evaluation of machine‑learning methods for power system protection. It defines 12 protection and event‑analysis functions across four grids (20–345 kV) as 24 scored tasks, enabling structured assessment under varied observability, distribution shifts, and cross‑grid transfer scenarios. The benchmark includes committed data partitions, leakage controls, and reproducible reporting, and demonstrates that wider observability does not always help, that shifted conditions expose hidden failures, and that fault detection transfers better than fault localization.
By Julian Oelhaf, Georg Kordowich, Christian Bergler, Andreas Maier, Johann J\"ager, Siming Bayer
arXiv:2607. 16031v1 Announce Type: cross Abstract: Data-driven pre-fault dynamic security assessment (DSA) rapidly evaluates the dynamic risk of credible contingencies on a power system using machine learning.
By Olayiwola Arowolo, Maosheng Yang, Jochen Cremer
The paper tackles fault detection and stability assessment during power swings in a 9‑bus WSCC system using PSCAD/EMTDC. It extracts 3,286 statistical, temporal, spectral, and fractal features from 3‑phase relay data via three feature libraries, then prunes them to 18 key descriptors with Boruta, RFECV, and SHAP. Benchmarking 14 classifiers, Rotation Forest and SVM‑RBF achieve near‑perfect discrimination of fault types and swing stability, demonstrating that automated, library‑driven feature engineering combined with rigorous statistical testing yields highly accurate, interpretable models.